Breaker fuse at outlet 10amp. tripped several Time while using kettle. Changed that weak hot fuse up to 15Amp. Is it fault repair or what to do next?
Kettle plug can be used with the other outlets directly source.
Answer ( 1 )
Please briefly explain why you feel this answer should be reported.
first thing you wanna know is how many M is that kettle drawing look for a tag on your kettle and see if it has an amp rating on it as well. You can’t just change a fuse or a breaker to a higher amperage without being in compliance with the wire itself so for instance, a 15 amp breaker would use a 14 wire and a 20 amp breaker would use a 12 wire